WHAT'S MOTOR DUTY CYCLE?

Learn more with our Quick Guide

IEC (the International Electrotechnical Commission) uses different duty cycles designations to describe electrical motor operating conditions.

The term duty defines the load cycle to which the machine is subjected, including, if applicable, starting, electric braking, no-load and rest de-energized periods, and including their durations and sequence in time.

Benevelli Group has a propriety software program that allows us to quickly search specific duty cycles to make sure to give customers the best fit.

It's responsibility of the manufacturers to declare the duty.

Electric Motor Duty Cycles

The IEC 60034 standard defines the electric motors standard duty cycles.

According to this standard, S2 duty rating is short time duty: motors using this duty cycle adapt to constant load.

Temperature rises fast during the operation and quickly reaches its limit. Motor needs stop for total cooling between each start. 

  • S1

    Continuous running duty

    The duty type S1 can be defined as operation at a constant load maintained for sufficient time to allow the machine to reach thermal equilibrium.

    For a motor suitable to this duty type, the rating at which the machine may be operated for an unlimited period is specified.

    This class of rating corresponds to the duty type whose appropriate abbreviation is S1.


    Figure 1 – Continuous running duty: Duty type S1

    Where: ΔT – Time sufficient to allow the machine to reach thermal equilibrium

  • S2

    Short Time Duty

    The duty type S2 can be defined as operation at constant load for a given time, less than that required to reach thermal equilibrium, followed by a time de-energized and at rest of sufficient duration to re-establish the equilibrium between the machine temperature and that of the coolant temperature.

    For a motor suitable to this duty type, the rating at which the machine, starting at ambient temperature, may be operated for a limited period is specified. This class of rating corresponds to the duty type whose appropriate abbreviation is S2.

    A complete designation provides the abbreviation of the duty type followed by an indication of the duration of the duty (S2 40 minutes).


    Figure 2 – Short-time duty: Duty type S2

    ΔTc – Operation time at constant load
    ΔT0 – Time de-energize

  • S3

    Intermittent periodic duty

    The duty type S3 is defined as a sequence of identical duty cycles, each including a time of operation at constant load and a time de-energized and at rest. The contribution to the temperature-rise given by the starting phase is negligible.

    A complete designation provides the abbreviation of the duty type followed by the indication of the cyclic duration factor (S3 30%).


    Figure 3 – Intermittent periodic duty: Duty type S3

    ΔTc – Operation time at constant load
    ΔT0 – Time de-energized and at rest
    Cyclic duration factor = ΔTc/T

  • S4

    Intermittent periodic duty with starting

    The duty type S4 is defined as a sequence of identical duty cycles, each cycle including a significant starting time, a time of operation at constant load and a time de-energized and at a rest.

    A complete designation provides the abbreviation of the duty type followed by the indication of the cyclic duration factor, by the moment of inertia of the motor JM and by the moment of inertia of the load JL, both referred to the motor shaft (S4 20% JM = 0.15 kg m2 JL = 0.7 kg m2).


    Figure 4 – Intermittent periodic duty with starting: Duty type S4

    ΔT* – Starting/accelerating time
    ΔTc – Operation time at constant load
    ΔT0 – Time de-energized and at rest
    Cyclic duration factor = (ΔT* + ΔTc)/ T

  • S5

    Intermittent periodic duty with electric braking

    The duty type S5 is defined as a sequence of identical duty cycles, each cycle consisting of a starting time, a time of operation at constant load, a time of electric braking and a time de-energized and at a rest.

    A complete designation refers to the duty type and gives the same type of indication of the previous case.


    Figure 5 – Intermittent periodic duty with electric braking: Duty type S5

    ΔT* – Starting/accelerating time
    ΔTc – Operation time at constant load
    ΔTf – Time of electric braking
    ΔT0 – Time de-energized and at rest
    Cyclic duration factor = (ΔT* + ΔTc + ΔTf)/ T

  • S6

    Continuous-operation periodic duty

    The duty type S6 is defined as a sequence of identical duty cycles, each cycle consisting of a time of operation at constant load and a time of operation at no-load. There is no time de-energized and at rest.

    A complete designation provides the abbreviation of the duty type followed by the indication of the cyclic duration factor (S6 30%).


    Figure 6 – Continuous-operation periodic duty: Duty type S6

    ΔTc – Operation time at constant load
    ΔT0 – Operation time at no load
    Cyclic duration factor = ΔTc/ΔT0

  • S7

    Continuous-operation periodic duty with electric braking

    The duty type S7 is defined as a sequence of identical duty cycles, each cycle consisting of a starting time, time of operation at constant load and a time of electric braking. There is no time de-energized and at rest.

    A complete designation provides the abbreviation of the duty type followed by the indication of both the moment of inertia of the motor JM and the moment of inertia of the load JL (S7 JM = 0.4 kg m2 JL = 7.5 kg m2).


    Figure 7 – Continuous-operation periodic duty with electric braking: Duty type S7

    ΔT* – Starting/accelerating time
    ΔTc – Operation time at constant load
    ΔTf – Time of electric braking
    Cyclic duration factor = 1

  • S8

    Continuous-operation periodic duty with related load/speed

    The duty type S8 is defined as a sequence of identical duty cycles, each consisting of a time of operation at constant load corresponding to a predetermined speed of rotation, followed by one or more times of operation at other constant loads corresponding to different speeds of rotation.

    A complete designation provides the abbreviation of the duty type followed by the indication of the moment of inertia of the motor JM and by the moment of inertia of the load JL, together with the load, speed and cyclic duration factor, for each speed condition (S8 JM = 0.7 kg m2JL = 8kgm2 25kW 800rpm 25% 40kW 1250rpm 20% 25 kW 1000 rpm 55%).


    Figure 8 – Continuous-operation periodic duty with related load/speed: Duty type S8

    ΔT* – Starting/accelerating time
    ΔTc1; ΔTc2; ΔTc3 – Operation time at constant load
    ΔTf1; ΔTf2 – Time of electric braking
    Cyclic duration factor = (ΔT*+ΔTc1)/T; (ΔTf1+ΔTc2)/T; (ΔTf2+ΔTc3)/T

  • S9

    Duty with non-periodic load and speed variations

    The duty type S9 is defined as a duty in which generally load and speed vary non-periodically within the permissible operating range. This duty includes frequently appplied overloads which may greatly exceed the reference load.

    For a motor suitable to this duty type, the rating at which the machine may be operated non-periodically is specified. This class of rating corresponds to the duty type whose appropriate abbreviation is S9.


    Figure 9 – Duty with non-periodic load and speed variations: Duty type S9

    ΔT* – Starting / accelerating time
    ΔTs – Time under overload
    ΔTc – Operation time at constant load
    ΔTf – Time of electric braking
    ΔT0 – Time de-energized and at rest

  • S10

    Duty with discrete constant loads and speeds

    The duty type S10 is defined as the operation characterized by a specific number of discrete values of load maintained for a sufficient time to allow the machine to reach thermal equilibrium. The minimum load during a duty cycle may have value zero and be relevant to a no- load or rest condition.

    A complete designation provides the abbreviation of duty type followed by the indication of the per unit quantities p/Δt for the partial load and its duration, and by the indication of the per unit quantity TL which represents the thermal life expectancy of the insulation system related to thermal life expectancy in case of duty type S1 with rated output, and by quantity r which indicates load for a time de-energized and at rest (S10 p/Δt = 1.1/0.4; 1/0.3; 0.9/0.2; r/0.1 TL = 0.6).


    Figure 10 – Duty with discrete constant loads and speeds: Duty type S10

    ΔΘ1; ΔΘ2; ΔΘ2 – Difference between the temperature rise of the winding at each of the various loads within one cycle and the temperature rise based on duty cycle S1
    ΔΘref – Temperature at reference load based on duty type S1 t1; t2; t3; t4: time of a constant load within a cycle P1; P2; P3; P4: time of one load cycle

So basically, intermittent duty applications have less heat to dissipate, which generates space, weight, and cost savings because a smaller sized motor can typically be used.

For example, in an application where a specific speed-torque point is required but the duty cycle is for 6 seconds every minute, a smaller motor may work for the application in comparison to the motor required for continuous operation. As a result, the duty cycle frequently determines the required motor size for a given application.

When purchasing a motor, it is important to consider the required operation and declare the duty cycle.

This ensures the proper motor is selected for the application. For more information on motor duty cycles and to select the best motor for your application, contact an Applications Engineer at Benevelli today.

 

Credits Electric Engineering Portal

“Generally speaking, the volume of a motor is proportional to the amount of heat that can be dissipated"

Questions?

Contact us

  • +39 0522 626350


© e-comer Srl · VAT IT 02993980354 · Cookie policy · Privacy Policy